Inside a charger

The building blocks of an AC wallbox and a DC fast charger, what each one does, and where its behaviour becomes visible in a Control Pilot log or a network capture.

The AC wallbox

An AC charger does not convert energy. It switches the mains through to the car, tells the car how much current it may draw, and protects the person holding the cable. The converter that charges the battery is the onboard charger in the car.

  • Supply and protection: a miniature circuit breaker, and residual current protection that also sees smooth DC fault current. The installation rules allow either a type A RCD combined with a 6 mA DC fault detector (an RDC-DD after IEC 62955), or a type B RCD. A plain type A device alone can be blinded by DC leakage from the onboard charger.
  • Contactor: switches all live conductors (L1 to L3 and N) and closes only when the car asks for energy in state C.
  • Control Pilot generator and measurement: a +12 V / -12 V source behind a 1 kilohm resistor, a PWM output and an ADC that reads the plateau voltages to tell the states apart.
  • Proximity (PP) reading: for a detachable cable, a measuring circuit that reads the coding resistor in the plug to learn the cable rating.
  • Energy meter: in Europe normally a MID approved AC meter; in Germany it must also meet calibration law (see Energy metering).
  • Controller: the state machine that ties it together, usually with an OCPP link to a backend and a user interface (RFID reader, display, LEDs).
  • Optional high level communication: an SECC running ISO 15118 with a HomePlug Green PHY modem, for example one of the Qualcomm QCA7000 family, coupled onto the Control Pilot wire.

The Control Pilot generator

The pilot is the one signal every conductive charger shares, AC or DC. The charger drives a 1 kHz square wave between +12 V and -12 V through its source resistor; the car loads it with a diode and resistors, which pulls the positive level down to 9 V, 6 V or 3 V. The negative level stays at -12 V because the car's diode blocks it, which is how the charger tells a real car from a short. The duty cycle carries the available current, or 5 percent to ask for digital communication.

A PLC modem shares this wire. The Green PHY carrier sits between about 2 and 30 MHz and rides on top of the PWM, so a logged pilot waveform with a wide bandwidth shows it as noise on the plateaus. The values and tolerances are covered on the IEC 61851-1 page; the checks CP-01 to CP-10 judge them.

The DC charger

  • AC/DC front end: a three phase rectifier with power factor correction that produces an internal DC link, often around 700 to 800 V.
  • Isolated DC/DC power modules: resonant or phase shifted converters with a high frequency transformer, so the output floats with respect to earth. Modules of about 20 to 50 kW are stacked in parallel; the output range of current chargers is typically about 150 or 200 V up to 920 or 1 000 V.
  • Output contactors on DC+ and DC-, and usually a discharge circuit that brings the output voltage down after a session.
  • Pre-charge: the power stage itself raises the output to the battery voltage while the current is held very low, so the car can close its contactors without an inrush.
  • Isolation monitoring device (IMD): measures the resistance between each output pole and protective earth, before and during charging.
  • DC meter: measures at the output, where calibration law applies, with compensation for the loss in the cable.
  • Cable and connector: above roughly 200 to 250 A continuous, liquid cooled cables are common; temperature sensors next to the DC contacts let the charger derate.
  • SECC: the communication controller for DIN SPEC 70121, ISO 15118-2 and ISO 15118-20 (or a CAN controller for CHAdeMO and GB/T), which turns the car's requests into set points for the power modules.

The DC link voltage, module sizes and cable current above which cooling is needed vary between makers. They are typical figures, not values from a standard.

What each part looks like in a capture

ComponentWhat it doesWhat it looks like in a capture
Control Pilot generatorAnnounces states and currentCP states and duty cycle in a CP log; 5 percent before SLAC (CP-04), E or F pulse on a retry (CP-05)
PP measurementReads the cable ratingThe pp or pp_ohm column; a missing class is reported by PP-01
PLC modemCarries IP over the pilotSLAC messages, attenuation values (SL-05, SL-06), then SDP and TCP
SECC softwareRuns the protocol state machineEvery V2G message and its response time (TIM-01), response codes (SQ-05)
AC contactorSwitches the mains to the carCurrent appears after PowerDeliveryRes Start and state C (PW-02) and falls after Stop (PW-03)
RCD or RDC-DDCuts the supply on a fault currentCurrent drops to zero with no protocol stop; often followed by state F or a controller reset
Power modulesDeliver the DC current and voltageEVSEMaximumPowerLimit in ChargeParameterDiscoveryRes; EVSEPowerLimitAchieved and EVSECurrentLimitAchieved in the charge loop
IMDChecks the insulation of the output and cableDuration of the CableCheck loop, EVSEIsolationStatus, EVSE_IsolationMonitoringActive while it measures
Pre-chargeMatches the output to the batteryThe PreCharge loop: EVSEPresentVoltage climbing towards EVTargetVoltage
DC output contactorsConnect the output to the cableCurrent after PowerDeliveryRes Start; the voltage falling during WeldingDetection
MeterCounts energy for billingMeterInfo in ChargingStatusRes, CurrentDemandRes or the ISO 15118-20 loop (PW-04)
Cooling and temperature sensorsKeep contacts and cable within limitsA falling EVSEMaximumCurrentLimit in a long session, with EVSECurrentLimitAchieved set

Sources

  • IEC 61851-1:2017, Annex A (Control Pilot circuit) and Annex B (proximity)
  • IEC 61851-23, DC charging stations: isolation monitoring, pre-charge and output switching
  • IEC 62955:2018, residual direct current detecting devices (RDC-DD)
  • IEC 60364-7-722, installation requirements for EV supply