Bidirectional charging: V2H, V2B, V2G and V2L in practice
Where cars give power back: a house during an outage, a building at its peak, the grid through an aggregator, a device on the camp site. Which standards carry it (ISO 15118-20 BPT, CHAdeMO), which grid connection rules apply, what the backend needs, and what to check in a capture.
The settings
| Use | Setting | Who is involved | Main value |
|---|---|---|---|
| V2L | Tools, camping, a house appliance plugged into the car | Driver, car maker | Power where there is no grid |
| V2H | A house with a bidirectional charger, behind the meter | Owner, installer, network operator | Backup power, own solar used at night |
| V2B | An office or depot, behind the meter | Site owner, fleet operator | Lower peak demand of the building |
| V2G | Any site, energy sold to the grid or a market | Aggregator, energy supplier, network operator | Payments for flexibility and energy |
The Bidirectional charging: V2G, V2H, V2L page defines the terms and compares AC and DC bidirectional charging. The short version: with DC the inverter is in the charger, which is certified once as a generating unit; with AC the onboard charger of the car runs backwards and the car must follow the grid code of wherever it is plugged in.
Standards and grid rules by region
| Region | Car to charger | Grid connection |
|---|---|---|
| Europe (Europe: AFIR, Type 2, CCS2 and ISO 15118) | ISO 15118-20 DC_BPT, and AC_BPT with the grid code exchange of Amendment 1 | EN 50549-1 and national rules such as VDE-AR-N 4105 in Germany. The EPBD recast asks that recharging points in buildings support bidirectional charging where appropriate. |
| North America (North America: J1772, CCS1, J3400 and the NEVI standards) | ISO 15118-20; SAE J3072 for onboard inverters on AC | IEEE 1547-2018, tested to IEEE 1547.1 and listed to UL 1741 supplement SB; California Rule 21 |
| Japan (Japan: CHAdeMO, Type 1 and the 300,000 port target) | CHAdeMO with the inverter in the V2H unit | National interconnection rules for the V2H unit |
- UL 9741, harmonized with CSA C22.2 No. 348, covers off board unidirectional and bidirectional equipment rated up to 1000 V AC and 1500 V DC that transfers energy between the car and off board loads, or runs in parallel with the grid, through a permanently attached vehicle connector (Safety and type approval of chargers and cars).
- The CHAdeMO Association lists version 1.1 (2015) as the protocol version that allowed smaller cable diameters for V2H.
- OCPP 2.1, released in January 2025, adds support for ISO 15118-20 and functional blocks for bidirectional charging and DER control (OCPP certification).
Not confirmed for this page and therefore not stated: the date of the current UL 9741 edition, the CHAdeMO version and V2H guideline that first introduced discharging, and the dates and partners of V2G pilots and tariffs in Europe and Asia. Check them against the standard bodies and the pilot operators before citing.
How a bidirectional session runs
- EVSE: ServiceDiscoveryRes, lists DC_BPT or AC_BPT beside the one directional service
- EV: ServiceSelectionReq, selects the BPT service and a parameter set
- EV: DC_ChargeParameterDiscoveryReq, BPT variant: charge and discharge limits
- both: ScheduleExchange, scheduled or dynamic control
- EV: DC_ChargeLoopReq, power flows in either direction within both sets of limits
Bidirectional power transfer in ISO 15118-20, message by message follows each message with its fields. Two points matter in the field: the car only discharges within the limits it announced, and the charger only draws power in a session that selected a BPT service.
Backend and what fails
- The discharge decision comes from outside the cable: a home energy manager for V2H, a building controller for V2B, an aggregator for V2G. It reaches the charger over OCPP or a local protocol and reaches the car as a schedule or as dynamic targets (Smart charging: schedules, limits and grid signals).
- Metering counts both directions. ISO 15118-20 carries a charged and a discharged energy reading; billing and grid settlement need both.
- Typical faults seen in captures: a charger that draws more than the discharge target of the car (the bpt-limit demo), a charger that draws power in a session without a BPT service, a car that announces discharge limits it then does not honour, and a control mode that changes mid session.
- On the grid side, a unit that does not disconnect when the grid fails, or that runs with the wrong national settings, is a safety problem for the network operator. That is outside the charging protocol and outside any capture of it.
What to record and test
- The ISO 15118-20 capture with the TLS key log (ISO 15118-20 requires TLS, which only a test bench switches off), the DC voltage and current with their sign, and the energy readings in both directions.
- For CHAdeMO V2H, the CAN frames of the session.
- Tests: charge and discharge at several power levels, a change of direction within the session, a discharge target the charger lowers during the loop, a grid loss in island capable V2H, and an emergency stop while discharging. DC test cases, worked has the DC forms.
In this tool
- The bpt-limit demo is an ISO 15118-20 session in which the car asks for 20 A of discharge and the charger draws 32 A; Worked example: discharge above the target in ISO 15118-20 reads it step by step. The iso20 demo shows a charger that offers DC and DC_BPT and a car that selects DC.
- IS20-01 checks that the messages match the selected service, IS20-03 that the charger stays inside the announced charge and discharge limits, IS20-04 that it stays at or below the target of the car, and IS20-05 that power flows back only in a bidirectional session. PW-04 checks that the charged energy reading never goes backwards; the discharged reading is not checked yet.
- The chademo demo shows a CHAdeMO session from CAN frames. Discharge frames of the later CHAdeMO versions are listed but not checked.
Sources
- ISO 15118-20:2022, services AC_BPT and DC_BPT; BPT variants of the parameter and charge loop messages
- Directive (EU) 2024/1275 on the energy performance of buildings (recast), Article 14, infrastructure for sustainable mobility
- AVERE: Guide to the revised Energy Performance of Buildings Directive, April 2024; recharging points, pre-cabling, smart and bidirectional charging
- CHAdeMO specification, V2H and bidirectional extensions, as summarised on the v2x page
- CHAdeMO Association: protocol development, version 1.1 (2015) with smaller cable diameters for V2H
- UL 9741, ANSI webstore, scope
- UL 9741, CSA store, harmonized CSA and ULSE standard
- Open Charge Alliance: Annual Report 2025, release of OCPP 2.1 at the start of 2025
- Open Charge Alliance: OCPP 2.1 accepted by IEC as IEC 63584-210
- IEEE 1547-2018 and UL 1741 SB, interconnection and listing of distributed energy resources in the US
- SAE J3072, onboard inverter systems interconnected with the grid
- VDE-AR-N 4105 and EN 50549-1, generating units on the low voltage grid in Germany and Europe